Input Indicating Lamps are glowing? |
NO |
YES |
IS AC SUPPLY VOLTAGE AVAILABLE |
IS AC VOLTAGE AVAILABLE AT THE INPUT
OF THE RECTIFIER
BRIDGE |
NO |
YES |
NO |
YES |
a) Check for input
supply failure. |
a) Check the lamp ballast
resistance (R) and
lamps, . |
a) Check AC contactors |
a) Check Thyristors / diode by
measuring the Anode – Cathode
resistance |
b) Check the possible
fault which could be
an earth fault or short
circuit in the Charger. |
|
b) If even after energizing the
Contactor no output results then
check the transformer
secondary voltage. |
b) Check the electronic control
circuit provided for automatic operations. |
|
|
c) If secondary voltage is O.K.
then check the semiconductor
protection fuses. |
c) Auto/Manual selector is
selected in Manual Mode and potentiomete-rs are kept in
minimum position. Adjust
potentiometers. |